Physical Data

Model UCW/H Module and Compressor

30

50

70

85

Capacity (tons) ¹

31.7

51.5

67.2

82.8

kW/Ton

0.738

0.746

0.744

0.740

Full-Load EER

2

16.3

16.1

16.1

16.2

Refrigerant Circuits (quantity)

2

2

2

2

Compressor Type

Scroll

Scroll

Scroll

Scroll

Compressor Quantity

2

2

2

2

Compressor Nominal Hp (per circuit)

15

25

35

40

Refrigerant Charge (per circuit) R-410A (lbs)

15

32

34

40

Module Operating Weight w/Water (lbs)

3

1480

2200

2450

2855

Module Shipping Weight (lbs)

4

1290

1880

2130

2390

30

50

70

85

Heat Exchanger (type)

Brazed Plate

Brazed Plate

Brazed Plate

Brazed Plate

Independent Refrigerant Circuits (quantity)

2

2

2

2

Water Storage Volume HX Only (gals)

3.2

6.1

7.3

11.4

Water Storage Volume HX Plus Main Headers (gals)

13.1

16.7

17.9

26.2

Min

30

50

70

85

Max

165

250

250

485

Maximum Design Working Pressure - Water Side (psi)

300

300

300

300

Header Water Connections - Inlet/Outlet (inches)

6

6

6

6

8

30

50

70

85

Heat Exchanger (type)

Brazed Plate

Brazed Plate

Brazed Plate

Brazed Plate

Independent Refrigerant Circuits (quantity)

2

2

2

2

Water Storage Volume HX Only (gals)

2.8

5.1

6.5

9.7

Water Storage Volume HX Plus 6" Main Headers (gals)

12.8

15.7

17.1

24.5

Min

40

65

85

100

Max

165

250

250

350

System Volume (gals)

8

Min

180

300

420

510

Maximum Design Working Pressure - Water Side (psi)

300

300

300

300

Header Water Connections - Inlet/Outlet (inches)

6

6

6

6

8

Notes:

1.

2.

3.

4. Unit shipping weight includes refrigerant charge, compressor oil and packaging.

5.

6.

7.

8. Required to provide stable operation. Storage/buffer tanks in return piping may be utilized to meet the minimum volume requirements.

Main header water/fluid connections are 6" grooved coupling for the 30, 50 and 70 ton modules. The 85 ton module uses 8" grooved couplings.
85 ton module cannot be directly coupled with 30, 50 or 70 ton modules due to a difference in header and frame size.

Module operational weight includes water, compressor oil, and refrigerant charge. Multiply times the number of modules for a total system
operational weight.

Tonnage ratings conditions: 44°F leaving chilled water temperature, 85°F entering condenser water temperature, flow rates are 3 gpm per ton
through the condenser with a fouling factor of .00025 hr-ft2-°F/Btu and 2.4 gpm per ton through the evaporator with a .0001 hr-ft2-°F/Btu fouling
factor.

Ratings in accordance with AHRI Standard 550/590.

The minimum/maximum flow rates are based on an approximate temperature differential of 5°F to 20°F through the evaporator and 5°F to 30°F
through the condenser. Flow rates vary based on application; verify with selection software.

Model UCW/H Condenser

Flow Rate (gpm)

5

Model UCW/H Evaporator

Flow Rate (gpm)

5