Refrigeration circuit diagram, Heat recovery, Title – ClimaCool UCW_H 30, 50, 70, 85 User Manual

Page 37

Advertising
background image

35

www.climacoolcorp.com

Refrigeration Circuit Diagram

SIZE

ClimaCool Corp.

CCE-08001-2.VSD

DWG NO

CCE-08001-2.VSD

REV

SHEET

1 OF 1

TITLE

REFRIGERATION CIRCUIT DIAGRAM

DATE

DRAWN BY

Gus Olivera

SCALE

NONE

A

FILENAME

CCE-08001-2.vsd

REVISED

C

APPROVED

DATE

04/2012

DESCRIPTION

UCW/H WATER COOLED SCROLL CHILLER

(REFRIGERANT CIRCUIT #1 OF 2 SHOWN

)

SYMBOL LEGEND

= TEMPERATURE SENSOR

= LEGEND ITEM #

= SOLDER JOINT

= PRESSURE TRANSDUCER

= "TEE" SOLDER JOINT

= REFRIGERANT FLOW PATH

= PRESSURE ACCESS FITTING

LL = LIQUID LINE
SL = SUCTION LINE
SP = SUCTION PRESSURE
HP = HEAD PRESSURE
TXV = THERMAL EXPANSION VALVE
DX = DI RECT EXPANSION
W/C = WAT ER COOLED

TXV

BULB

EQUALIZER

LINE

FLUSH

SHUT-OFF

VALVE

CHILLER

WATER INLET

VALVE

CHILLER

WATER OUTLET

VALVE

S4

S5

S2

S3

CONDENSER

WATER PIPING

CHILLER

WATER PIPING

1

2

5

6

7

8

9

4

RE

FRI

G

ERA

NT

CI

RCUI

T #2

RE

FRI

G

ERA

NT

CI

RCUI

T #1

RE

FRI

G

ERA

NT

CI

RCUI

T #1

RE

FRI

G

ERA

NT

CI

RCUI

T #2

3

COMPONENT LEGEND

1.

SCROLL COMPRESSOR

2.

HIGH PRESSURE SAFETY SW.

3.

HOT GAS BYPASS VALVE

4.

W/C BRAZED PL. CONDENSER

5.

PRESSURE RELIEF VALVE

6.

LIQUID LINE FILTER DRIER

7.

SIGHT GLASS MOISTURE INDICATOR

8.

THERMAL EXPANSION VALVE

9.

W/C BRAZED PL. EVAPORATOR

S1.

DISCHARGE TEMPERATURE SENSOR

S2.

COND. INLET TEMPERATURE SENSOR

S3.

COND. OUTLET TEMP. SENSOR

S4.

EVAP. INLET TEMPERATURE SENSOR

S5.

EVAP. OUTLET TEMP. SENSOR

S6.

SUCTION TEMPERATURE SENSOR

PT1.

DISCHARGE PRESSURE TRANSDUCER

PT2.

SUCTION PRESSURE TRANSDUCER

FILL

SHUT-OFF

VALVE

CHILLER OUTLET

WATER MAIN

(6"or 8")

CHILLER INLET

WATER MAIN

(6"or 8")

FILL

SHUT-OFF

VALVE

CONDENSER

WATER INLET

VALVE

CONDENSER

WATER OUTLET

VALVE

FLUSH

SHUT-OFF

VALVE

CONDENSER

OUTLET

WATER MAIN

(6" or 8")

CONDENSER

INLET

WATER MAIN

(6" or 8")

PETE'S

PORTS

PETE'S

PORTS

PT2

PT1

(WHEN USED)

(WHEN USED)

EQUALIZER

LINE

(WHEN USED)

(WHEN USED)

(WHEN USED)

(WHEN USED)

(WHEN USED)

(WHEN USED)

(WHEN USED)

(WHEN USED)

#

PT#

S #

S1

(WHEN USED)

S6

(WHEN USED)

Heat Recovery