Verify the unit nameplate voltage agrees
with the power supply. Connect power and
control field wiring as shown on the unit
specific wiring diagram provided with the
unit.

Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 167°F (75°C).

Route power and control wiring, separately,
through the utility entry. Do not run power
and signal wires in the same conduit.

Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the

current

National

Electric

Code,

ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.

Power wiring is to the unit terminal block or
main disconnect. All wiring beyond this
point has been done by the manufacturer and
cannot be modified without effecting the
unit's agency/safety certification.















Figure 11 - Terminal Block


Startup technician must check motor
amperage to ensure that the amperage listed
on the motor nameplate is not exceeded.
Motor overload protection may be a function
of the variable frequency drive and must not
be bypassed.

Note: All units are factory wired for
208/230V, 460V, or 575V. If unit is to be
connected to a 208V supply, the transformer
must be rewired to 208V service. For 208V
service interchange the yellow and red
conductor on the low voltage control
transformer.
Red-Black for 208V
Yellow-Black for 230V

Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.

If any factory installed wiring must be
replaced, use a minimum 221°F (105°C)
type AWM insulated conductors.


Electric

shock

hazard.

Before

attempting to perform any installation,
service, or maintenance, shut off all
electrical power to the unit at the
disconnect switches. Unit may have
multiple power supplies. Failure to
disconnect power could result in
dangerous operation, serious injury,
death or property damage.

WARNING