2 messages - faults, 1 messages, Messages – DE DIETRICH C 230 Eco User Manual

Page 13

Advertising
background image

13

20/02/09 - 300015144-001-C

C 230 ECO

6.2 Messages - Faults

6.2.1

Messages

Message

Code

no.

Probable causes

Action

SHOW REM. CTRL

The message SHOW REM.CTRL indicates
the presence of an override on a remote
control

To cancel the overrides on all remote controls, press the
AUTO key for 5 seconds

REVISION

Boiler service required

Contact the professional responsible for maintenance of the
boiler

BL.PSU ERROR

0

Error parameters

- Switch the boiler off and switch back on
- Set the boiler type parameter (See #CONFIGURATION)

BL.MAX BOILER

1

Boiler temperature > 110 °C

Wait 10 minutes for the temperature to come down

BL.MAX EXCHAN

3

Heat exchanger temperature > 95 °C

- Wait 10 minutes for the temperature to come down
- Check the water flow
- Check that the installation and boiler are adequately filled

with water and correctly irrigated and bled

- Check: Heat exchanger fouled

BL.DERIVE EXCH

4

The speed at which the exchanger
temperature is rising is too high

- Wait 10 minutes for the temperature to come down
- Check the water flow
- Check that the installation and boiler are adequately filled

with water and correctly irrigated and bled

- Check: Heat exchanger fouled

BL.DT EXC.BACK

5

The temperature difference between the
exchanger sensor and the return sensor is
too great (35 K)

- Wait 10 minutes for the temperature to come down
- Check the water flow
- Check that the installation and boiler are adequately filled

with water and correctly irrigated and bled

- Check: Heat exchanger fouled

BL.DT BOI.EXC.

6

The temperature difference between the
boiler sensor and the exchanger sensor is
too great

- Wait 10 minutes for the temperature to come down
- Check the water flow
- Check that the installation and boiler are adequately filled

with water and correctly irrigated and bled

- Check: Heat exchanger fouled

BL.RL OPEN

8

The RL inlet on the PCU is open

- Switch the boiler off and switch back on
- Set the boiler type parameter (See #CONFIGURATION)

BL.INV. L/N

9

- Phase and neutral inverted
- Mains electricity with floating or two-phase

neutral

- Respect the rating plate on the connection terminal block
- Set the boiler type parameter (See #CONFIGURATION)

BL.CS OPEN

11

The contact inlet CS is open

Check the cause of the open contact CS

BL.COM PCU-M3

13

Communication breakdown between PCU
and DIEMATIC-m3

Check the link and the connectors

BL.GAS PRESS

15

Gas pressure too low

Check:

- Opening the gas valve on the boiler
- Gas supply pressure
- Correct installation of the pressure switch (Replace if

necessary)

BL.BAD SU

16

The SU is not compatible with the PCU

- Switch the boiler off and switch back on
- SU: Change them

BL.PCU ERROR

17

Error parameters

- Switch the boiler off and switch back on
- PCU: Change them