DE DIETRICH C 230 Eco User Manual

Page 16

Advertising
background image

16

C 230 ECO

20/02/09 - 300015144-001-C

TA-S FAILURE

Internal problem.

- Switch off the current.
- Contact the professional responsible for maintenance of

the boiler.

PSU FAIL

0

PSU not connected or faulty

- Reset the box
- Check the link and the connectors
- PSU: Replace if necessary

PSU PARAM FAIL

1

Safety parameter errors

- Reset the box
- Check the link and the connectors
- PSU: Replace if necessary

STB EXCHANGE

5

Exchanger temperature too high

- Reset the box
- Check that the installation and boiler are adequately

filled with water and correctly irrigated and bled

- Check: Heat exchanger fouled

STB BACK

9

Return temperature too high

- Reset the box
- Check that the installation and boiler are adequately

filled with water and correctly irrigated and bled

- Check: Heat exchanger fouled

EXCH-BACK<MIN

10

- The temperature difference between the

exchanger sensor and the boiler flow
sensor is too little

- Sensor defective
- No flow rate or flow rate too low
- Sensor installed incorrectly

- Reset the box
- Check that the installation and boiler are adequately

filled with water and correctly irrigated and bled

Check:

- Heat exchanger fouled
- Sensor installed correctly
- Level differences on the temperature sensors

EXCH-BACK>MAX

11

- The temperature difference between the

exchanger sensor and the boiler flow
sensor is too great

- Sensor defective
- No flow rate or flow rate too low
- Sensor installed incorrectly

- Reset the box
- Check that the installation and boiler are adequately

filled with water and correctly irrigated and bled

Check:

- Heat exchanger fouled
- Sensor installed correctly
- Level differences on the temperature sensors

SMOKE.P.FAIL

12

- The flue gas pressure switch is open
- Bad connection
- The pressure in the combusted gases

evacuation duct is too high

- Reset the box
- Check the wiring
- Ensure that the siphon is not empty. Top up with more

water if necessary

- It is possible that the combustion products evacuation

pipe is totally or partially obstructed

- Check: Open flue damper

Faults

Code no.

Probable causes

Action

Advertising