BURNER FAILURE

14

- No flame after 5 ignition attempts
- No ignition spark

- Reset the box
- Check the correct connection of the ignition cable and

that there is no breakdown or short circuit on the earth

Check:

- the gap between the electrodes (3 to 4 mm)
- Burner cover status (Burner / electrode cover closed)
- Faulty control by the SU board

- No flame after 5 ignition attempts
- No flame

- Reset the box
- First check that the gas valve is open, that the gas

supply pressure is present, that the gas conduit has
been sufficiently bled, that the air/flue gas conduit is not
blocked and is not leaking, that the siphon is full and not
blocked

- The gas valve unit must be set with precaution
- Gas block: Wiring OK
- Faulty control by the SU board

- No flame after 5 ignition attempts
- Flame present (insufficient ionization)

Check the correct connection of the ignition cable and that
there is no breakdown or short circuit on the earth
Check:

- Check the electrode condition
- Opening the gas valve on the boiler
- Gas supply pressure

CCE TEST FAIL

15

- The cyclical leak proofing kit (CCE) has

detected a leak

- Reset the box
Check:

- Opening the gas valve on the boiler
- Gas supply pressure
- Replace the gas valve (If necessary)

PARASIT FLAME

16

Detection of a parasite flame

- Reset the box
Check:

- Ignition/ionization electrode
- Leak on the gas valve
- Gas inlet valve closed (Compulsory)

VALVE FAIL

17

Gas valve defective

- Reset the box
- Check the link and the connectors
- Check the gas valve and replace if necessary

FAN FAILURE

34

The fan is not running at the right speed

- Reset the box
Check:

- Cabling error
- Fan error

BACK>BOIL FAIL

35

The return temperature is higher than the
boiler temperature

- Reset the box
- Check the water circulation direction in the boiler
- Check that the boiler sensor and the return sensor have

not been reversed

I-CURRENT FAIL

36

The flame went out more than 5 times in 24
hours while the burner was operating

- Reset the box
Check:

- Gas supply pressure
- Pressure regulator
- Setting the gas valve unit

SU COM.FAIL

37

Communication breakdown between PCU
and SU

- Reset the box
- Check the installation of the SU on the PCU

PCU-M3 COM.FAIL

38

Communication breakdown between PCU
and DIEMATIC-m3

- Reset the box
- Check the link and the connectors

Faults

Code no.

Probable causes

Action