The last ten failures are memorised in the paragraph #DEF.
HISTORY

Z

See: "Parameter and input/output check (mode tests) - Control

panel instructions

Comments

OUTSI. S.FAIL.

The boiler operates on BOILER MAX temperature

- The valve setting is no longer ensured but monitoring the maximum

temperature of the circuit after the valve is ensured.

- Valves may be manually operated.

- Reheating the domestic hot water remains ensured.

DHW S. FAILURE

The hot water storage tank reheating operation is no longer assured.

OUTL S.A FAIL., OUTL S.B FAIL. and OUTL S.C FAIL.

The circuit concerned goes from automatic to manual mode: The pump
operates.

ROOM S.A FAIL., ROOM S.B FAIL. and ROOM S.C FAIL.

The circuit concerned operates without any influence from the room sensor.

SWIM.P.A S.FAIL, SWIM.P.B. S.FAIL, SWIM.P.C. S.FAIL

Pool reheating is independent of its temperature.

SOLAR S. FAIL

Reheating domestic hot water using the solar panel is no longer ensured.

ST.TANK S.FAIL

The hot water storage tank reheating operation is no longer assured.

TAS...

Domestic hot water production is shut down and can be restarted using key



.



The tank is no longer protected.
Contact the professional responsible for maintenance of the
boiler.



A tank without Titan Active System® is connected to the boiler: Check
that the Titan Active System® simulation connector (delivered with
package AD212) is fitted to the sensor card."