GETTING AROUND PODVIEW® 

Step Eight 

Changing a Pump Set Point:  EchoPod® sensor models with relays have (1‐4) channels.  If after accessing the 
MENU, PUMP appears in the display, then at least (1) relay is configured for pump or valve control.  Simplex 
pump  control  has  (1)  ON  and  (1)  OFF  setting.    Duplex  pump  control  (2‐pumps)  has  a  third  additional  LAG 
setting.  Note: Prior to making any changes, we recommend that you write down all existing set point values.  
The example below highlights a duplex pump system in an automatic empty or automatic fill operation with 
(1) LAG, (1) ON and (1) OFF set point.  Use the following steps to change your simplex or duplex pump control 
settings. 

Automatic Empty Operation 

 

 

Automatic Fill Operation 

 

Steps to Change Pump Set Points

1. Hold SELECT for 5 seconds to enter the MENU. 
2. Press SELECT when PUMP appears. 

3. Press SELECT when the set point (ON, OFF, LAG) you want to 

change appears. 

4. Press the UP and DOWN buttons to increase or decrease the 

set point to the desired value.  To scroll faster, hold SELECT 
while pressing UP or DOWN. 

5. To enter the set point, hold SELECT for 2 seconds. 

6. To change another set point, press SELECT when the set 

point appears. 

7. To exit the MENU, press SELECT when RUN appears. 

Tech Tips 

 Never place a relay set point (ON, OFF, LAG) at the liquid empty or liquid full position.  You should have 

at least some distance or volume buffer separating them. For example, in a 500 gallon tank, the relay 
set points could be placed at ≥ 10 gallons or ≤ 490 gallons. 

 