GETTING AROUND PODVIEW® 

Step Eight 

Changing an Alarm Set Point:  EchoPod® sensor models with relays have (1‐4) channels.  If after accessing the 
MENU, ALARMS appears in the display, then at least (1) relay is configured as an alarm.  The Alarm settings 
may  be  in any  combination  of  LOW  and/or  HIGH  alarms  (4‐HIGH,  1‐LOW  &  3‐HIGH,  2‐LOW  &  2‐HIGH,  etc.).  
Note:  Prior  to  making  any  changes,  we  recommend  that  you  write  down  all  existing  set  point  values.    The 
example below highlights a 2‐LOW and 2‐HIGH alarm operation with (4) set points.  Use the following steps to 
change your alarm settings. 

 

Steps to change Alarm settings: 
1. Hold SELECT for 5 seconds to enter the MENU. 

2. Press SELECT when ALARMS appears. 

3. Press SELECT when the set point (HIGH2, HIGH 1, LOW1, LOW2) you want to change appears. 

4. Press  the  UP  and  DOWN  buttons  to  increase  or  decrease  the  set  point  to  the  desired  value.    To  scroll 

faster, hold SELECT while pressing UP or DOWN. 

5. To enter the set point, hold SELECT for 2 seconds. 

6. To change another set point, press SELECT when the set point appears.  

7. To exit the MENU, press SELECT when RUN appears. 

Hints: 

 Never place a relays set point (High 1, Low 1) at the liquid empty or liquid full position.  You should 

have at least some distance or volume buffer separating them.  For example, in a 500 gallon tank, the 
relay set points could be placed at ≥ 10 gallons or ≤ 490 gallons. 

 

  
 
 
 
 

 