TROUBLESHOOTING 

Step Nine 

Display Descriptors: The following are the display’s operational descriptors, meaning and corrective action: 

WARMUP

WARMUP is seen when power is first applied to the EchoPod® and PodView®.  WARMUP 
indicates that the display is waiting for the EchoPod® to acquire and send a valid level 
reading.

MENU

Indicates the menu for configuration of relay set points.

PUMP

PUMP is the identifier for the relay set points affecting Pump or Valve operations. 

 

OFF

OFF is the relay set point that turns OFF the pump.

 

ON

ON is the relay set point that turns ON the pump. 

 

LAG

LAG is the set point that turns ON the lag pump.

ALARM

Alarm is the identifier for the relay set points affecting Alarm operations.

 

HIGH #

HIGH # is the relay set point that energizes a high alarm relay.

 

LOW #

LOW # is the relay set point that energizes a low alarm relay.

CHECK WIRES

Not All four wires are properly connected to the EchoPod®.  Check the wiring between the 
PodView® and the EchoPod®.

UPDATE FW REV

The attached EchoPod® is not running a version of the firmware (50.0 or higher) that is 
compatible with PodView®.  Connect the EchoPod® to WebCal® 6.0 and update the 
firmware.  


 

 

 
 

 