Installation, Start-up – Burkert Type 2712 User Manual

Page 9

Advertising
background image

9

Assembly

7.2. installation

Warning!

risk of injury from improper installation!
Damaged parts or incorrect tightening torques can cause leaks on
the equipment.
• Use an open-end wrench for the assembly.
• Observe the tightening torque (see torque table).

7.2.1. installing the body

Any installation position, preferably with handwheel face up.
welded body:

Weld valve body in pipeline system.

other body designs:

Connect valve body to pipeline.

7.2.2. installing the actuator (Welded body)

Check graphite seal and, if required, replace. Ensure that sealant

residue cannot get into the pipeline system.

Graphite seal

Lubricate the nipple thread before reinstalling the actuator
(e.g. with Klüberpaste UH1 96-402 produced by Klüber).

Observe the torques when screwing the actuator into the valve
body (see “Tab. 1”).

orifice (dn)

15

20

25

32-40

50-65

tightening
torque ± 3 [nm]

45

50

60

65

70

Tab. 1: Torque for screwing into the valve body

8. start-up

For commissioning observe type label specifications and information
on media, media pressure and temperature values in chapter “5.
Technical data”
.

english

Types 2000, 2012, 2702, 2712

Advertising
This manual is related to the following products: