4

auTOrizEd usE

3.

Non-authorized use of the solenoid valve Type 6211
EV may be a hazard to people, nearby equipment
and the environment.

The device is designed to control, shut off and meter

neutral media up to a viscosity of 21 mm

2

/s.

Provided the cable plug is connected and installed

correctly, e.g. Bürkert Type 2507, the device satisfies

protection class IP65 in accordance with

DIN EN 60529 / IEC 60529.
During use observe the authorized data, the opera-

ting conditions and conditions of use specified in the

contract documents, on the rating plate and in the

operating instructions, as described in the chapter

entitled “

6.Technical Data”.

Correct transportation, correct storage and installation

and careful use and maintenance are essential for

reliable and faultless operation.
Use the device only as intended.

english

5

predictable misuse

3.1.

The device may only be used in the explosion-protected

area if an appropriate additional identification is attached
to the rating plate.
Do not put any loads on the housing (e.g. by placing objects

on it or standing on it).
Do not make any external modifications to the device hou-

sings. Do not paint the housing parts or screws.
The solenoid coil must not be thermally insulated, as it

heats up during operation. Ensure that the solenoid coil is
adequately ventilated.

restrictions

3.2.

If exporting the system/device, observe any existing
restrictions.

english

6

basic safETy

4.

insTrucTiOns

These safety instructions do not make allowance for any:

contingencies and events which may arise during the

installation, operation and maintenance of the devices.
local safety regulations – the operator is responsible for

observing these regulations, also with reference to the
installation personnel.

Danger – high pressure!

Before loosening the pipes and valves, turn off the

pressure and vent the pipes.

Risk of electric shock!

Before reaching into the device or the equipment,

switch off the power supply and secure to prevent

reactivation!
Observe applicable accident prevention and safety

regulations for electrical equipment!

Risk of burns/risk of fire if used for a prolonged
switch-on time through hot device surface!

Keep the device away from highly flammable substan-

ces and media and do not touch with bare hands.
Do not thermally insulate the unit and provide adequate

ventilation.

english

7

Risk of injury due to malfunction of valves with
alternating current (AC).
Sticking core causes coil to overheat, resulting in a
malfunction.

Monitor process to ensure function is in perfect working

order!

Risk of short-circuit/escape of media through leaking
screw joints.

Ensure seals are seated correctly!

Carefully screw valve and connection lines together!

General hazardous situations.
To prevent injury, ensure that:

the system cannot be activated unintentionally.

Installation and repair work may be carried out by

authorized technicians only and with the appropriate

tools.
After an interruption in the power supply or fluid sup-

ply, ensure that the process is restarted in a defined or

controlled manner.