Burkert Type 1115 User Manual

Page 6

Advertising
background image

6

3.3

Connector pin assignment

D sub-connector 9 terminal/female

5

9

6

1

RS 232

RS 485 / Profibus

2

TxD

3

reception/transmission data

positive
3

RxD

8

reception/transmission data

negative
5

GND

5

GND

3.4

Installation

The maximum bus baud rate is 500 KBaud.
The following performance lengths can be achieved:

1200 m 9.6 / 19.2 / 93.75 KBaud
600 m

187.5 KBaud

200 m

500 KBaud

twisted double-wiring, shielded

Notice:

standard wiring diameter 0.22 mm

2

for additional information refer to the

doubled wiring length at 0.5 mm

2

Profibus standard DIN 19245

To operate, remove equipment from the mains supply. Remove plastic inset from back of
equipment and insert interface card.
After reconnecting to mains supply, the following settings are necessary in serial menu
supplements:

1. address

(for Profibus, the baud rate adjusts automatically)

2. additionally for RS 232/485:

parity / odd / even / none
baud rate 4800 / 9600

Advertising