Alarms, Causes and actions to be taken error codes – Burkert Type 8056 User Manual

Page 35

Advertising
background image

SE56

35

CODES ERROR

DESCRIPTIONS

ACTION TO TAKE

0001

problem with watch-dog circuit

ADDRESS TO SERVICE

0002 wrong

configuration work data in eeprom

0004 wrong

configuration

safety data in eeprom

0008 defective

eeprom

0010

defective keyboard (one or more key are pushed during the test)

0020

Power supply voltage (+3.3) is out of range

0040

Power supply voltage (+13) is too low (<10V)

0080

Power supply voltage (+13) it’s too high (>14V)

0200

timeout calibration input (input circuit is broken)

0400

Input stage gaining is out of range

Check the status of the cables connecting the sensor to
the transmitter, the grounding connections of the
devices or the possible presence of strong and
anomalous noise sources

0800 Interruption

on

the coils circuit

Check the status of the cables connecting the sensor to
the transmitter

0C00

Cumulative alarm 0800 + 0400

see single code

ALARMS

Messages

ERRORS

ACTION TO TAKE

NO ALARMS

All works regularly

-----

MAX ALARM

The flow rate is higher than the maximum threshold set

Check the maximum flow rate threshold set and the
process conditions

MIN ALARM

The flow rate is lower than the minimum threshold set

Check the minimum flow rate threshold set and the
process conditions

FLOW RATE >FS

The flow rate is higher than the full scale value set on the
instrument

Check the full scale value set on the instrument and
the process conditions

PULSE/FREQ>FS

The pulse generation output of the device is saturated and cannot
generate the sufficient number of impulses

Set a bigger unit of volume or, if the connected
counting device allows it, reduce the pulse duration
value

EMPTY PIPE

The measuring pipe is empty or the detection system has not
been properly calibrated

Check whether the pipe is empty or perform again
the empty pipe calibration procedure

BATCH ALARM

Batch interrupted for the followings condition:

‰

Timer batch expired before the end of the
batch

‰

Batch valve open and flow rate to zero for a
time longer to the safety timer set

‰

batch valve closed and flow rate different from
zero for a time longer to the safety timer set

Verify:

‰

presetting

‰

system condition

INPUT NOISY

The measure is strongly effected by external noise or the cable
connected the transmitter to the sensor is broken

Check the status of the cables connecting the sensor,
the grounding connections of the devices or the
possible presence of noise sources

EXCITATION FAIL The coils or the cable connecting the sensor are interrupted

Check the connecting cables to the sensor

CURR. LOOP

OPEN

The 0/4...20mA output on board or the optional one are not
correctly closed on a valid load

Verify the load is applied to the output (max 1000
ohm).

To disable the alarm,set the “mA VAL.FAULT” value (
menu alarm ) to 0.

P.SUPPLY FAIL

Power supply different from that suitable in the label.

Verify that the power supply is that suitable on label

Causes and actions to be taken

Error codes

Advertising
This manual is related to the following products: