Technical data, Conformity, Operating conditions – Burkert Type 8070 User Manual

Page 11: General technical data, Mechanical data, Electrical data

Advertising
background image

9

TechnicalData

6.

Technical DaTa

6.1.

conformity

The device is approved by EC and conforms to the standards mentioned on the EC declaration of conformity.

6.2.

Operating conditions

Ambient temperature (operating)

-10 °C...+60 °C

Protection class

IP65 according to EN 60529, the device being wired and the
cable gland tightened or the female connector plugged-in and
tightened

Combined flow sensor

• Flow transmitter 8022

• Pulse divider 8022

• only Bürkert flow sensors types 8020 Low Power, 8030 Low

Power or 8070 Low Power.

• any flow sensor 8020 with pulse output, 8030 with pulse

output or 8070 with pulse output.

6.3.

general technical data

6.3.1. mechanical data

Dimensions

70 x 32 x 42,5 mm (L x l x H)

Fastening

• device without display and configuration unit
• device with display and configuration unit

• 1 M3 x 35 screw
• 1 M3 x 45 screw

Housing material

polyamide/polycarbonate

Material of the seals

• seal for the sensor fixed connector
• seal for the cover

• NBR
• EPDM

6.3.2. electrical data

Electrical connection

• 4-pin terminal strip, 1.5 mm

2

max. wire section, 6 - 7 mm cable diameter

• M12 male fixed connector

Supply voltage

V+ : 12-30 V DC +- 10%, residual ripple < 5%

Frequency input

1-600 Hz, sensor power supply approx. V+ - 1 V

4-20 mA output

• Accuracy
• Min. voltage drop at the device

terminals

• Loop impedance

• +/- 1,5% of the full scale
• < 10 V at 20 mA

• max. 100 W at 12 VDC, max. 700 W at 24 VDC, max. 1000 W at 30 VDC

NPN/PNP output

• Accuracy

open collector, 50 mA max. current, frequency up to 600 Hz

• +/- 1% of the measured value

Power consumption

< 200 mW

English

Type 8022

Advertising
This manual is related to the following products: