Maintenance, troubleshooting, Maintenance work, Error messages – Burkert Type 8070 User Manual

Page 23: Default values

Advertising
background image

21

Maintenance,Troubleshooting

10.

mainTenance, TrOuBleshOOTing

10.1. maintenance work

The flow transmitter / pulse divider Type 8022 is maintenance-free when operated according to these operating instructions.

10.2. error messages

Error messages are only displayed at the Read level. They are shown alternately (flashing) with the process value.

error

cause

troubleshooting

ERR1

Value cannot be displayed
(e.g. value too high).

• Change the fow rate unit

(see chapter 9.4.1. Unit – Setting the unit for the
flow rate
).

ERR2

Input frequency of sensor higher than 600 Hz.

• Use a suitable sensor.

ERR3

Calculated output current not within range of 4-20
mA or K factor = 0.

• Correctly set the flow rate range associated to the

4-20 mA current output.

• Use a different sensor and/or correctly set the K

factor of the fitting used.

ERR4

Limit values of the flow rate range associated to the
4-20 mA current output not correct (Low > High).

Correctly set the values.

ERR5

The K factor times the set volume (converted in liters)
pro pulse is < 1.

• Check the set K factor.
• If the K factor is correct, enter a higher volume pro

pulse so that the K factor times the set volume
(converted in liters) pro pulse is equal to or higher
than 1.

Tab. 2: Error messages

10.3. Default values

Upon delivery, the following default values are saved:

parameter

Value

Unit

Liters/second [l/s]

K factor (of fitting used)

1 pulse/liter [imp/l]

Volume pro pulse

1 liter

Output signal (

OUT)

4-20 mA

Lower flow rate limit

0 liters/second [l/s]

Upper flow rate limit

250 liters/second [l/s]

Tab. 3: Default values

English

Type 8022

Advertising
This manual is related to the following products: