Burkert Type 8025 User Manual

Page 18

Advertising
background image

18

Installation and wiring

Type 8025 UNIVERSAL

terminal block 1
PE:▶factory▶wired▶shield.
terminal block 2
•▶ Iout:▶4-20▶mA▶output▶(green▶wire,▶factory▶wired)
•▶ L+:▶V+▶(red▶wire,▶factory▶wired)
•▶ L-:▶0V▶(black▶wire,▶factory▶wired)
•▶ PE:▶protective▶earth,▶factory▶wired
•▶ P-:▶negative▶transistor▶output▶(brown▶wire,▶factory▶wired)
•▶ P+:▶positive▶transistor▶output▶(white▶wire,▶factory▶wired)
terminal block 3 "flow sensor": Wiring▶the▶remote▶flow▶sensor.▶
The▶wiring▶depends▶on▶the▶type▶of▶output▶signal▶originating▶from▶the▶
flow▶sensor:▶see▶chap.▶„7.4.10“.

Switch▶

A

:▶see▶„Fig.▶15“▶page▶21

Switch▶

B

:▶see▶chap.▶„7.4.10“

Switch▶

C

:▶see▶„Tab.▶1“▶page▶29

Switch▶

D

:▶see▶chap.▶„7.4.10“

Switch▶

E

:▶see▶chap.▶„7.4.4“

terminal block 4:▶Wiring▶of▶the▶relay▶output▶DO2▶(if▶the▶device▶has▶
relays).
terminal block 5:▶Wiring▶of▶the▶relay▶output▶DO3▶(if▶the▶device▶has▶
relays).
terminal block 6
•▶ Terminal▶5:▶4-20▶mA▶output▶(AO1)
•▶ Terminal▶6:▶positive▶27▶V▶DC▶power▶supply,▶available▶to▶energize▶an▶

external▶instrument

•▶ Terminal▶7:▶0V▶(earth▶of▶the▶power▶supply▶available▶to▶energize▶an▶

external▶instrument)

•▶ Terminal▶8:▶protective▶earth:▶shields▶of▶the▶AO1▶and▶DO1▶output▶

cables

•▶ Terminal▶9:▶Negative▶transistor▶output▶(DO1)
•▶ Terminal▶10:▶Positive▶transistor▶output▶(DO1)
terminal block 7:▶Wiring▶of▶the▶115/230▶V▶AC▶power▶supply▶

Mark▶

8

:▶time-delay▶fuse▶to▶protect▶the▶115/230▶V▶AC▶power▶supply

Fig. 10: Terminal assignment of a wall-mounted version, 115/230 V AC

English

Advertising