Adjustment and commissioning

Type 8025 UNIVERSAL

8.7

Entering the k factor of the fitting used

The▶device▶determines▶the▶flow▶rate▶in▶the▶pipe▶using▶the▶fitting▶K▶factor.
The▶K▶factor▶of▶the▶fitting▶used▶can▶be▶entered▶here.▶The▶device▶may▶also▶determine▶the▶K▶factor▶using▶a▶Teach-In▶procedure:▶See▶the▶com-
plete▶operating▶instructions.

The▶device▶will▶use▶the▶new▶K▶factor▶as▶soon▶as▶"SAVE▶YES"▶is▶confirmed▶when▶leaving▶the▶Parameters▶menu.

The▶K▶factor▶of▶the▶fitting▶used▶is▶in▶the▶operating▶instructions▶of▶the▶fitting.
The▶operating▶instructions▶of▶the▶Bürkert▶fittings▶can▶be▶found▶on▶the▶CD▶delivered▶with▶the▶device▶or▶on▶the▶internet▶at▶

www.burkert.com

.

The▶display▶shows▶the▶K▶factor▶of▶the▶
fitting,▶last▶entered▶or▶determined▶using▶
a▶Teach-In▶procedure.

Edit▶the▶parameter.

K-FACtOR

K=10.000

REtURN

Enter▶the▶K▶factor▶(value▶between▶0.01▶and▶
99999.9)▶of▶the▶fitting▶used.

Confirm▶the▶displayed▶value.

K=2.8500

OUtPUt

VALiD N/Y

Is▶only▶displayed▶if▶the▶K▶factor▶has▶been▶changed.

Confirm▶the▶entered▶K▶factor▶or▶not.

Fig. 27: Entering the K factor of the fitting used