Fig.▶25, Fig.▶26, Sensor type – Burkert Type 8025 User Manual

Page 29: Sensor

Advertising
background image

29

Installation and wiring

Type 8025 UNIVERSAL

Selector▶ D ▶makes▶it▶possible▶to▶configure▶the▶type▶of▶sig-
nal▶the▶8025▶Universal▶receives▶from▶the▶flow▶sensor.

Set▶the▶selector▶on▶the▶right▶
(default▶position)▶when▶the▶
signal▶from▶the▶flow▶sensor▶
which▶is▶connected▶to▶the▶▶
8025▶Universal▶is▶either:

•▶ a▶pulse▶signal,▶NPN▶or▶PNP
•▶ an▶"on/off"▶signal▶(Reed▶relay▶for▶

example)

•▶ a▶0-5▶V▶DC▶standard▶voltage▶

signal▶(TTL,▶for▶example)

Set▶the▶selector▶on▶the▶
left▶when▶the▶signal▶
from▶the▶flow▶sensor▶
which▶is▶connected▶to▶
the▶▶8025▶Universal▶is▶a▶
sine-wave▶signal▶(coil).

D

SENSOR TYPE

COIL

NPN/PNP

SENSOR TYPE

COIL

NPN/PNP

Fig. 25: Using selector "SENSOR TYPE"

When▶selector▶"SENSOR▶TYPE"▶above▶is▶set▶on▶"NPN/PNP",▶
selector▶

B

▶▶makes▶it▶possible▶to▶configure▶the▶supply▶voltage▶for▶

the▶flow▶sensor.

SENSOR

SUPP

LY

+5V

L+

(L+)-12V

B

If▶the▶8025▶Universal▶is▶energized▶with▶a▶115/230▶V▶AC▶power▶
supply,▶set▶selector▶"SENSOR▶SUPPLY"▶on▶"L+"▶(default▶
position).

If▶the▶8025▶Universal▶is▶energized▶with▶a▶12-36▶V▶DC▶
power▶supply,▶set▶the▶voltage▶selector▶"SENSOR▶SUPPLY"▶
depending▶on▶the▶voltage▶supply▶needed▶by▶the▶remote▶flow▶
sensor:▶"+5V",▶"L+"▶or▶"(L+)-12V"▶(default▶position).

Fig. 26: Using selector "SENSOR SUPPLY"

Tab. 1: Default positions of selectors "SENSOR SUPPLY",

"LOAD" and "SENSOR TYPE"

Selector

Default▶position

SENSOR▶SUPPLY▶(

B

)▶

L+

LOAD▶(

C

)

2.2KOhms

SENSOR▶TYPE▶(

D

)

NPN/PNP

English