3 technical data, English – Burkert Type S039 User Manual

Page 8

Advertising
background image

ENGLISH

ENGLISH

flow rate controller 8039

3

technical data

General features

Pipe diameter

DN6 to DN50 (1/4’’ to 2’’); determine the appropriate diameter using the

flow rate-velocity-DN diagrams (see Annex)

Fluid temperature

max. 100 °C

Fluid pressure

depends on the S039 fitting (see the corresponding fitting manual)

Fluid viscosity

max. 300 cSt

Rate of solid particles

max. 1%

Measuring range

0,3 m/s to 10 m/s (

1.0 to 32 fps), 0.3 m/s (1.0 fps) corrresponds to a flow rate of 0,5 l/min

(

0.2 gpm) in a DN6 (1/4’’) fitting.

Accuracy

±1 % of the full scale*, with calibration on site or using the teach-in function

± (1 % of the full scale* + 3% of the measured value), with standard K factor

Linearity

± 0.5 % of the full scale*

Repeatability

0.4% of the measured value

Measuring element

paddle-wheel of the S039 fitting

Protection rating (housing)

IP 65, cable plugs being plugged-in and tightened

* Full scale = 10 m/s

electrical features

Installation class
(overvoltage class)

2

Insulating strength

2300 VAC

Power supply

12-30 VDC

Current consumption
Version with PNP output

max.750 mA + consumption of the load, if the PNP output is connected

max. 50 mA + consumption of the load, if the PNP output is not connected

Version with relay output

max. 80 mA, without load