6 set up, 1 general information, 2 adjustment elements – Burkert Type 8112 User Manual

Page 20: 6set up

Advertising
background image

6

Set up

6

.1 General information

The figures in brackets refer to the following illustrations.

The switching condition of the electronics can be checked with closed
housing cover (control lamp). In the basic setting, products with a
density > 0.7 g/cm³ (0.025 lbs/in³) can be detected. For products with
lower density, the switch must be set to > 0.5 g/cm³ (0.018 lbs/in³).

On the electronics module you will find the following indicating and
adjustment elements:

l

Signal lamp (1)

l

DIL switch for characteristics reversal - min./max. (2)

l

DIL switch for sensitivity adjustment (3)

l

Simulation key (4)

Note:
For test purposes, immerse the tuning fork of LEVEL SWITCH 8112
always in liquids. Do not test the function of LEVEL SWITCH 8112 with
your hand. This can damage the sensor.

6

.2 Adjustment elements

1

5

2

3

4

Fig. 12: Oscillator SWE60N - NAMUR output

1

Signal lamp (LED)

2

DIL switch for characteristics reversal

3

DIL switch for sensitivity adjustment

4

Simulation key

5

EMC filter element

Function/Configuration

20

LEVEL SWITCH

8112 • with NAMUR output

6 Set up

32052

-EN