Burkert Type 8112 User Manual

Page 31

Advertising
background image

1

2

-50 °C

(-58 °F)

0 °C

(32 °F)

50 °C

(122 °F)

100 °C

(212 °F)

150 °C

(302 °F)

200 °C

(392 °F)

250 °C

(482 °F)

20

(290)

-1 (-14,5)

40

(580)

64

(928)

Fig. 27: Process temperature - Process pressure with switch position 0.5 g/cm³ (sensitivity switch)

1

Process pressure in bar (psig)

2

Process temperature in °C (°F)

Viscosity - dynamic

0.1 … 10,000 mPa s (requirement: with density 1)

Flow velocity

max. 6 m/s (with a viscosity of 1 mPa s)

Density

0.7 … 2.5 g/cm³ (0.025 … 0.09 lbs/in³); 0.5 … 2.5 g/
cm³ (0.018 … 0.09 lbs/in³) by switching over

Electrical protective measures

Protection rating

IP

66/IP 67

Overvoltage category

III

Protection class

II

Adjustment elements

Mode switch

-

Min.

rising characteristic curve (High current when
immersed)

-

Max.

falling characteristics (Low current when immersed)

Sensitivity switch

-

0.5

0.5 … 2.5 g/cm³ (0.018 … 0.9 oz/in³)

-

0.7

0.7 … 2.5 g/cm³ (0.025 … 0.9 oz/in³)

Test key

simulation of a line break between sensor and
processing unit

Voltage supply

Operating voltage (characteristics according
to standard)

for connection to an amplifier according to NAMUR
IEC

60947-5-6, approx. 8.2 V

Off-load voltage

U

0

approx. 8.2 V

Shortcircuit current

I

U

approx. 8.2 mA

LEVEL SWITCH

8112 • with NAMUR output

31

9 Supplement

32052

-

EN

-

120418