Error

Cause

Rectification

Wrong character-
istic selected

Set the correct characteristics on the
characteristics reversal switch (over-
flow protection, dry run protection).
Wiring should be carried out accord-
ing to the quiescent current principle.

Signal lamp
flashes red

Error on the vi-
brating element

Check if the vibrating element is
damage or extremely corroded.

Interference on
the electronics
module

Exchanging the electronics module

instrument defec-
tive

Exchange the instrument or send it in
for repair

Depending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.

7

.3 Exchange of the electronics

If the electronics module is defective, it can be replaced by the user.

In Ex applications only an electronics module with respective Ex
approval may be used.

You find all information to the electronics exchange in the operating
instructions of the new electronics module.

In general, all electronics modules of series SW60 can be inter-
changed. If you want to use an electronics module with a different
signal output, you carry out the complete setup. You find the
necessary, suitable operating instruction on our homepage.

Note:
Keep in mind that enamelled instrument versions need special
electronics modules. These electronics modules are called SW60E or
SW

60E1.

Reaction after fault rec-
tification

24

LEVEL SWITCH

8112 • with NAMUR output

7 Maintenance and fault rectification