3 wiring plan, single chamber housing – Burkert Type 8112 User Manual

Page 18

Advertising
background image

5

Open the terminals with a screwdriver

6

Insert the wire ends into the open terminals according to the wiring
plan

7

Tighten the terminals with a screwdriver

8

Check the hold of the wires in the terminals by lightly pulling on
them

9

Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable

10 Screw the housing cover back on

The electrical connection is finished.

5

.3 Wiring plan, single chamber housing

3

5

1

2

4

R

2 0 - 2 5 3 V A C

2 0 - 7 2 V D C

A

B

L

N

1 2

3 4 5

6 7 8

0,5 g / cm3

0,7 g / cm3

3 4 5 6 7 8

+

Fig. 10: Electronics and connection compartment, single chamber housing

1

Control lamp

2

DIL switch for mode adjustment

3

DIL switch for switching point adaptation

4

Ground terminal

5

Connection terminals

We recommend connecting LEVEL SWITCH 8112 in such a way that
the switching circuit is open when there is a level signal, line break or
failure (safe condition).

Information:
The relays are always shown in non-operative condition.

Electronics and connec-
tion compartment

Wiring plan

18

LEVEL SWITCH

8112 • - Relay (DPDT)

5 Connecting to power supply

32050

-EN