Pipe thread, cylindrical (DIN 3852-A)

G¾ A, G1 A

-

American pipe thread, conical
(ASME B1.20.1)

¾ NPT

or 1 NPT

-

Flanges

DIN from DN 25, ANSI from 1"

-

hygienic fittings

Bolting DN 40 PN 40, Clamp 1" DIN 32676
ISO

2852/316L, Clamp 1½" PN 10 DIN 32676

ISO

2852/316L, conus DN 25 PN 40, Tuchenhagen

Varivent DN 50 PN 10

Max. torque - process fitting

-

Thread G¾ A, ¾ NPT

75 Nm (55 lbf ft)

-

Thread G1 A, 1 NPT

100 Nm (73 lbf ft)

High voltage test (enamel)

max. 5 KV

Gas-tight leadthrough (optional)

-

Leakage rate

< 10

-6

mbar l/s

-

Pressure resistance

PN

64

Output variable

Output

Relay output (DPDT), 2 floating spdts

Turn-on voltage

-

Min.

10 mV

-

Max.

253 V AC, 253 V DC

Switching current

-

Min.

10 µA

-

Max.

3 A AC, 1 A DC

Breaking capacity

-

Min.

50 mW

-

Max.

750 VA AC, 54 W DC
If inductive loads or stronger currents are switched
through, the gold plating on the relay contact
surface will be permanently damaged. The contact
is then no longer suitable for switching low-level
signal circuits.

Contact material (relay contacts)

AgNi (Au plated) or AgSnO (Au plated)

Modes (switchable)

-

A

Max. detection or overflow/overfill protection

-

B

Min. detection or dry run protection

Measuring accuracy

Deviation

± 1

mm (0.04 in)

LEVEL SWITCH

8112 • - Relay (DPDT)

27