Error

Cause

Rectification

Buildup on the vibrating
element

Check the vibrating ele-
ment and the sensor if
there is buildup and re-
move it.

Wrong mode selected

Set the correct mode on
the mode switch (over-
flow protection, dry run
protection). Wiring
should be carried out
according to the quies-
cent current principle.

Signal lamp flashes red

Error on the vibrating
element

Check if the vibrating
element is damage or
extremely corroded.

Interference on the
electronics module

Exchanging the elec-
tronics module

instrument defective

Exchange the instrument
or send it in for repair

Depending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.

7

.3 Exchange of the electronics

If the electronics module is defective, it can be replaced by the user.

In Ex applications only an electronics module with respective Ex
approval may be used.

You find all information to the electronics exchange in the operating
instructions of the new electronics module.

In general, all electronics modules of series SW60 can be inter-
changed. If you want to use an electronics module with a different
signal output, you carry out the complete setup. You find the
necessary, suitable operating instruction on our homepage.

Note:
Keep in mind that enamelled instrument versions need special
electronics modules. These electronics modules are called SW60E or
SW

60E1.

Reaction after fault rec-
tification