Fail safe alarm setting – Fluid Components International FLT Series User Manual

Page 38

Advertising
background image

FLUID COMPONENTS INTL

CHAPTER 3 - OPERATION

FLTÔ Series FlexSwitchÔ

3 - 20

Doc. No. 06EN003246 Rev. B

Fail Safe Alarm Setting

These procedures set the second relay to detect component failure (fail-safe).

Low Flow Alarm Settings

For the low flow fail safe setup the following jumpers are to be installed: J18, J20, J23, J24, J27.

Figure 3-5. Low Flow Fail Safe Alarm

High Flow Alarm Settings

For the high flow fail safe setup the following jumpers are to be installed: J18, J20, J23, J25, J26.

Figure 3-6. High Flow Fail Safe Alarm

The following information is assumed:

Relay is de-energized in the ALARM condition.
Alarm 1 set point is adjusted for desired high flow alarm velocity or signal.
Alarm 2 set point is adjusted above maximum signal output (under range flow not to exceed 7.0 volts).

The following information is assumed:

Relay is de-energized in the ALARM condition.
Alarm 1 set point is adjusted for desired low flow alarm velocity or signal.
Alarm 2 set point is adjusted slightly below minimum signal output (over range flow).

0.5

0

2 0

1 0

3 0

5 0

4 0

6 0

1.0

0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

W H E N A L A R M 1 D E T E C T S L O W
F L O W T H E R E I S A P O S S I B L E O P E N
A C T I V E R T D O R S H O R T E D
R E F E R E N C E R T D

W H E N A L A R M 2 D E T E C T S O V E R
R A N G E F L O W , T H E R E I S A P O S S I B L E
H E A T E R F A I L U R E ,
S H O R T E D A C T I V E R T D O R
O P E N R E F E R E N C E R T D

SIGNAL

O U T P U T

AIR FLOW RATE

A L A R M 1 S E T P O I N T

A L A R M 2 S E T P O I N T

D E - E N E R G I Z E D

D E - E N E R G I Z E D

E N E R G I Z E D

E N E R G I Z E D

C00534-1

A P O W E R F A I L U R E I S D E T E C T E D I F
B O T H R E L A Y S A R E D E - E N E R G I Z E D

0 . 5

0

2 0

1 0

3 0

5 0

4 0

6 0

1 . 0

0

1 . 5

2 . 0

2 . 5

3 . 0

3 . 5

4 . 0

4 . 5

5 . 0

W H E N A L A R M 2 D E T E C T S A N
U N D E R R A N G E F L O W , T H E R E I S A
P O S S I B L E O P E N A C T I V E R T D O R
S H O R T E D R E F E R E N C E R T D

W H E N A L A R M 1 D E T E C T S H I G H
F L O W , T H E R E I S A P O S S I B L E
H E A T E R F A I L U R E ,
S H O R T E D A C T I V E R T D O R
O P E N R E F E R E N C E R T D

SIGNAL

OUTPUT

AIR FLOW RATE

A L A R M 2 S E T P O I N T

A L A R M 1 S E T P O I N T

D E - E N E R G I Z E D

D E - E N E R G I Z E D

E N E R G I Z E D

E N E R G I Z E D

C 0 0 5 3 5 - 1

A P O W E R F A I L U R E I S D E T E C T E D I F

B O T H R E L A Y S A R E D E - E N E R G I Z E D