Proportional action Y

P

Process variables: % / (mg/L, ppm)

Proportional action (Gradient K

C

[%])

Deviation

Neutral zone (Y=0)

Tolerated deviation from desired value.

Example: With the setting “010 %”, a deviation of

± 5 % does not activate the controller.

X

w

10 / (1.00)

20 / (2.00)

30 / (3.00)

40 / (4.00)

100 %

50 %

Co

nt

ro

lle

r

output Y

K

C

= 500

%

K

C

= 200

%

K

C

= 100

%

K

C

= 50

%

50 / (5.00)

with:
Y

P

Proportional action

T

R

Reset time [s]

T

D

Rate time [s]

K

C

Controller gain [%]

Constant

50 % (for % O

2

or % Air)

5.00 mg/L (for mg/L)

5.00 ppm (for ppm)

Controller equations

Controller output Y = Y

P

+ Y

P

dt + T

D

I action

D action

dY

P

dt

P action

1

T

R

Setpoint - Meas. value

Constant

Y

P

=

*

K

C