Front panel indicators and buttons, Ront, Anel – CTI Products NCB/AY with Serial Interface User Manual

Page 12: Figure 3 ncb front panel

Advertising
background image

CTI Products, Inc.

NCB-AY User Guide

1. Introduction

6

F

RONT

P

ANEL








1 2 3 4 5 6 7 8

ON

OPTION A

DC IN

ERR

ACT

PWR

NETWORK

OUT

IN

RSVC

CSVC

RESET

CMD

NCB

NETWORK COMBINER

NETWORK

Figure 3 NCB Front Panel

Front Panel Indicators and Buttons

PWR LED (Green) - Indicates condition of DC input power or a “Wink” command.

Always On: Correct DC input power is present.

Flashing Continuously: DC input to module is below minimum required voltage.

Flashes for 2 Seconds: A “Wink” network management command has been sent to the Control
Neuron Processor.

ERR LED (Red) – Indicates a possible error condition.

Always On: A diagnostic error has been detected. Press the “RESET” button. If the “ERR” LED now
stays off, the EEPROM contained invalid data and has been reinitialized. Any non-volatile
information must be re-entered by using the NCB/Plug Configuration Plug-in or the DOS NCBCON
program.

If the LED stays on solid, a hardware problem is indicated. Contact technical support for

assistance.

Slow Flash: (once per second) LonWorks configuration information is insufficient. Using a Network
Management Tool, re-commission the internal router nodes (and optionally, the Control Neuron
Processor node).

Quick Flash: (twice per second) A serial port configured for use (“BAUD” switch set to a value that is
not ‘0’) does not detect an attached modem or is in the process of initializing it. In Ring Mode, this
could also indicate that duplicate Unit Numbers have been detected in the Ring.

ACT LED (Yellow) - Indicates a packet has been passed by the NCB router.

LonWorks NETWORK Connections

RJ-45 and Screw Terminal

CMD Button Not Used
CSVC Button
Initiates Service Request

from Control Neuron

RSVC Button Initiates Service Request

from Router

RESET Button

DC IN Connector for input power

OPTION A Switches

Selects LonWorks
Addressing parameters.
(See Setup and
Operation
for more detail)

PWR LED Indicates correct input power
ERR LED

Indicates an error condition

ACT LED

Indicates LonWorks packet
activity in router

Advertising