CTI Products NCB/AY with Serial Interface User Manual

Page 46

Advertising
background image

CTI Products, Inc.

NCB-AY User Guide

Appendix D. Troubleshooting

40

A

PPENDIX

D.

T

ROUBLESHOOTING

Table D1

If the PWR LED . . .

REASON

CORRECTIVE ACTION

Is always illuminated.

Normal operation indicating that NCB unit

is receiving proper DC input power.

Go to next Table.

Flashes for 2 seconds.

Normal operation when WINK command is

being executed.

Go to next Table.

Flashes continuously.

DC input to unit is below minimum required

voltage.

Check for proper voltage at “DC IN”

connector (10-32VDC).

Does not illuminate.

NCB unit is not receiving DC input power.

Check for proper voltage at “DC IN”

connector (10-32VDC).

Table D2

If the ERR LED . . .

REASON

CORRECTIVE ACTION

Is always off.

Normal operation indicating no error

condition was detected.

Goto next Table.

Occasionally blinks on, then

off.

Normal operation when “CSVC” button or

“RSVC” button is pressed.

Go to next Table.

Flashes slowly, at a rate of

once every 2 seconds.

The Router Neurons are unconfigured.

Use a Network Management Tool to

‘Replace’ or ‘Commission’ router,
or
Use NODEUTIL to change the
mode/state to ‘Configured’ and ‘On-
line’,
or
Use SETRTR –F to configure the
router to Factory default conditions
(Repeater Mode).

Flashes quickly, at a rate of

twice per second.

1. A serial “PORT” is enabled, but is not

terminated correctly to an active device.

1a. Either disable the serial “PORT”

(setting the appropriate BAUD switch
to ‘0’, or

1b. Terminate the serial “PORT” in an

active device such as another NCB, a
modem, or terminal adapter.

Is always illuminated.

Router module, or Control Neuron

Processor, or Microprocessor is not
functioning.

Call CTI Products, Customer Support (+1-

513-595-5900), to arrange to return
unit for evaluation/repair.