Appendix D. Troubleshooting

42

Does not illuminate when

remote LonWorks nodes
are transmitting messages.

1. LonWorks message packets from remote

nodes are not passing through the remote
router module.





2. LonWorks message packets from remote

nodes are not reaching the local NCB.

3. LonWorks message packets from remote

nodes are not passing through the local
router module.

1a. Verify the connection between the

remote LonWorks nodes and the
remote NCB.

b. Verify that “ACT” LED on remote

NCB illuminates when remote
LonWorks nodes are transmitting
messages.

c. Place the remote router in Repeater

mode and verify that its “ACT” LED
illuminates when remote LonWorks
nodes are transmitting messages.

d. If ‘1c’ is ok, re-commission the remote

router.

e. If ‘1c’ is not ok, return unit for

evaluation/repair.

2.

See this Table above and verify that the
“ACT” LED “Does not illuminate
when “RSVC” button on remote NCB
is pressed”.

3.

See this Table above and verify that the
“ACT” LED “Does not illuminate
when “RSVC” button on remote NCB
is pressed”.

Table D4

Miscellaneous:

REASON

CORRECTIVE ACTION

Cannot communicate with

Control Neuron Processor
of local NCB when using
NODEUTIL.

1. In Bridge or Configured modes, router

neurons and network interface are not in
the same domain.

2. In Repeater mode, the network interface

may be defective.

1.

Verify that Nodeutil can communicate
with another LonWorks node.

2a. Place the local router neurons in

Repeater mode and verify that
communications is possible, or

b. Use Nodeutil to change the network

interface Domain to match the router
neurons’ domains.

Cannot communicate with the

Control Neuron Processor
of local NCB when using
NCBCON.

1. In Bridge or Configured modes, the

Control Neuron, the router neurons, and
the network interface are not all in the
same domain. (2)

2. In Repeater mode, the Control Neuron

and network interface are not in the same
domain. (1)

1.

Place the local router neurons in
Repeater mode.

2.

Use NCBCON to change the network
interface Domain to match the Control
Neuron domain.

Cannot commission the

Control Neuron
Processor when using
LonMaker for
Windows.

Incorrect external interface definition

(.xfb or .xif file) was specified when
commissioning node.

Use NCBTLC30 for Version 3 NCB

units.
Use NCBTLC20 for NCB units
prior to Version 3.