CTI Products NCB/IM with Internal PSTN Modem User Manual

Page 49

Advertising
background image

CTI Products, Inc.

NCB/IM User Guide

Appendix E. Troubleshooting

43

Table E5

If the ACT LED (on local

NCB) . . .

REASON

CORRECTIVE ACTION

Occasionally blinks on, then

off.

Normal operation indicating a message

packet has passed through the router
module of the NCB.

Go to next Table.

Does not illluminate when

“RSVC” button on remote
NCB is pressed.

1.

L

ON

W

ORKS

Service Pin message from

remote NCB is not reaching the local
NCB.


2.

L

ON

W

ORKS

Service Pin message from

remote NCB is not passing through the
local router module.

1a. Verify that “ACT” and “ERR” LED’s

on remote NCB flash once. If not,
return remote unit for
evaluation/repair.

b. Verify that “OH” and “CD” LED’s are

both illuminated on the local and
remote NCB’s. (See above)

2a. Place the remote router in Repeater

mode and verify that the local “ACT”
LED illuminates when “RSVC” button
on remote NCB is pressed.

b. If ‘2a’ is ok, re-commission the local

NCB router.

c. If ‘2a’ is not ok, swap either the local

or remote unit with a known-good-unit
to determine the faulty unit.

Does not illuminate when

local

L

ON

W

ORKS

nodes

are transmitting messages.

1.

L

ON

W

ORKS

message packets from

local nodes are not passing through the
local router module.

1a. Verify the connection between the

local

L

ON

W

ORKS

nodes and the local

NCB.

b. Place the local router in Repeater mode

and verify that its “ACT” LED
illuminates when local

L

ON

W

ORKS

nodes are transmitting messages.

c. If ‘1b’ is ok, re-Commission the local

NCB.

d. If ‘1b’ is not ok, return the local NCB

unit for evaluation/repair.

Does not illuminate when

remote

L

ON

W

ORKS

nodes are transmitting
messages.

1.

L

ON

W

ORKS

message packets from

remote nodes are not passing through the
remote router module.





2.

L

ON

W

ORKS

message packets from

remote nodes are not reaching the local
NCB.

3.

L

ON

W

ORKS

message packets from

remote nodes are not passing through the
local router module.

1a. Verify the connection between the

remote

L

ON

W

ORKS

nodes and the

remote NCB.

b. Verify that “ACT” LED on remote

NCB illuminates when remote

L

ON

W

ORKS

nodes are transmitting

messages.

c. Place the remote router in Repeater

mode and verify that its “ACT” LED
illuminates when remote

L

ON

W

ORKS

nodes are transmitting messages.

d. If ‘1c’ is ok, re-comminssion the

remote router.

e. If ‘1c’ is not ok, return unit for

evaluation/repair.

2.

See this Table above and verify that the
“ACT” LED “Does not illluminate
when “RSVC” button on remote NCB
is pressed”.

3.

See this Table above and verify that the
“ACT” LED “Does not illluminate
when “RSVC” button on remote NCB
is pressed”.