Flushing & charging – AMABILIA DOUBLE O-RING GEOTHERMAL FLOW CENTERS DORFC-2 User Manual

Page 18

Advertising
background image

Manual 2100-518B

Page

18 of 30

All Flushing of earth loops should be performed using a

1.5 HP or larger pump (as specified by IGSHPA). Flushing
can be accomplished using three different methods. The

first flushing method applies a one-step installation of the
loop, unit and inside piping. The second method allows a

Loop Contractor to use flush cart when installing the loop,
and at a later date, the dealer can install the unit to the

loop using only domestic water to flush the unit. The third
procedure shown is used when replacing the pump, coaxial
refrigerant to water coil, or unit. The following are step-by-
step procedures.

Be careful not to rotate the 3-way valves

into a position where air can be introduced into the loop.

Reflushing will be required if this occurs. Valve position

can be verified by looking on the end of the valve stem for
the pattern position.

Consult the IGSHPA for more complete flushing and

antifreeze instructions.
Flush in one direction for one hour, deadheading

in increments - checking site glass for air pockets.

Reverse flow in opposite direction, again for one hour,

deadheading in increments - checking site glass for air

pockets.

The presence of air can be detected by “deadheading” the
pump. To deadhead the pump, close off the return to the
pump and watch the water level site glass. Once you have
no more than 1/2" to 3/4" drop in the site glass, you will
have achieved complete air removal.

Power flushing can be achieved using the home’s city water

supply (or well water) connected to the flush cart. This

uses the combined pressure of the flush cart pump and the

home’s water system for faster flushing.

After flushing is complete, but prior to unit start up,

remove the large screw from the center of the flow center

pump(s) to allow air to escape (water will drip out).

Replace the screw after pump has filled with fluid.
For final pressurization, run the unit in heating or cooling
for a period of 20 minutes. Following this 20 minute run

time, pressurize the loop using the flush cart to 50-75 psig in
winter or 40-50 psig in summer.

In areas where entering loop temperatures drop below
40°F (5°C) or where piping will be routed through areas

subject to freezing, antifreeze is needed to prevent the loop

from freezing inside the pipe or heat exchanger. Alcohols

and glycols are commonly used as antifreeze, however,
you should consult with your distributor for assistance in

selecting the antifreeze best suited for your region.

PrOcedures fOr addinG

antifreeze

1. Flush cart should be half full of water.

2. Add measured amount of antifreeze through hose

below the water level (calculate based upon loop).

3. Add antifreeze to loop side only (see valve position in

Figure 9A).

4. Pump and dump (discharge).

5. Turn off pump; close discharge valve.

6. Repeat the procedure to add remaining antifreeze to
loop.

flushinG & charGinG

Advertising
This manual is related to the following products: