Flow center initial startup – AMABILIA DOUBLE O-RING GEOTHERMAL FLOW CENTERS DORFC-2 User Manual

Page 24

Advertising
background image

Manual 2100-518B

Page

24 of 30

1. Check to make sure the loop and unit isolation valves

are completely open and the flush ports are closed and

sealed (see Figure 9D).

2. Geothermal units have two low pressure switches

installed. One switch is intended for Ground Water

Applications (default factory wired - blue wires), and

the second is intended for Ground Loop Applications

(yellow wires). Remove the “blue” wires from the

LPS terminals of the compressor control module

internal of the control panel of the geothermal heat

pump and replace with the yellow low pressure switch

wires (see unit wiring diagram).

3. Check and record the earth loop pressure (use P/T

ports at geothermal heat pump).

Loop Pressure_____IN_____OUT

4. Check and record flow rate.

FLOW RATE - _____GPM

5. Check performance of unit. (Refer to Geothermal

Heat Pump Installation Manual.)

PrOcedure fOr PressurizinG the

system

1. Once system is completely flushed and antifreeze is

added, it can then be pressurized. Perform this by

deadheading the pump by closing the return hose ball

valve. This will increase the pressure on the loop via

the flush cart pump. As the pressure will fluctuate

with the seasons (set higher in winter and lower in

summer), it is suggested that the initial loop pressure

be 50-75 psig in winter and 40-50 psig in summer. If

you cannot reach these pressures with the flush cart

pump alone, turn on the fresh water feed to the cart

while still deadheading the pump. The potable water

pressure, along with the pump, will increase the

amount of pressure in the loop.

2. Bleed any air from the inside of the pump. This can

be done by removing the bleed screw from the center

of the pump motor head, allowing a small amount of

fluid to drip out. Replace the bleed screw.
3. Rotate the flow center valves to isolate the flush cart

from the rest of the system (see Figure 9D).

4. Turn off the flush cart pump, relieve the pressure on

the hoses and remove them.

5. Replace flow center access plugs and caps.

NOTE:

If the flow center is mounted in the horizontal

position, the supply hose must be connected to the lower

flushing port to allow air to pass out of the upper port

during the final flushing.

Pressure/temPerature PluGs

The pressure/temperature plugs (P/T plugs) supplied with
the ground water connectors are provided as a means of

measuring flow and temperature (see Figure 10). The

waterflow through the unit can be checked by measuring
the incoming water pressure at the supply pressure P/T and
subtracting the leaving water pressure at the return water
P/T plug. Comparing the differential to the pressure drop/

flow chart (Table 3) will determine the flow rate through
the heat pump.

Example: Model GV51S1 with a measured pressure

drop of 5.1 psig is equivalent to 9 GPM flow.

GPM rates higher than the required minimum flow rates will

not be detrimental to performance. However, insufficient

flow can significantly reduce capacity, efficiency and create
nuisance trips of safety controls, and possibly damage to
components in extreme conditions.

NOTE:

Pressure/Temperature probes should be lubricated

with a water-based lubricant prior to gently pushing the

probes into the P/T ports to prevent internal damage.

Thermometers, probes and gauges are available for

conducting these tests.

flOw center initial startuP

Advertising
This manual is related to the following products: