PIPInG WITh no valve

To Supply/Storage

Tank

single head bulk Plant air

eliminator with optical sensor

bIlls of MaTerIals

a8170

BOM on page 25

Condulet box

w/ optical

sensor

81947

optical sensor

(sensor only)

WIrInG To leCTroCoUnT

lCr-II or lCr 600

Optical Sensor

Out8/Black (54)

In5/White (55)

+Vo/Red (56)

84040 or 81920

CPU Board

WIrInG To MUlTIload

ToPTeCh PreseT

To configure the single head bulk Plant air

eliminator with optical sensor to Multiload:

1. Set the number of seconds in Low Flow Time Alarm to

the desired time between Optical Sensor detection of air

and the valve closing to stop the flow .

2. Configure custom logic: Set Output Port 8 active (Control

Valve Enable) when Input Port 9 is active.

A89501 - 3"

A89541 - 4"

A89561 - 6"