Installation

Wiring

Step 3 - Reassemble Cable Plug

Reinstall the terminal block into the cable plug housing in

the same orientation you found it. Tighten the strain relief

strap inside the cable plug using the two screws. Tighten the

cable gland on the bottom of the cable plug so that it seals

around the cable.
Reconnect the cable plug to the coil. Place the cover over

the cable plug and fasten with the screw to a torque of 8.8

in-lbs (1 Nm).

LC

3

Connections

Optical Sensor Connection

Wire Color

J11 Pin Connection

Red

33

White

34

Black

35

S3 Solenoid Connection

Terminal

J11 Pin Connection

1 (Red)

31

2 (Black)

32

Figure 11a: LCR-II to Optical Air Eliminator Wiring

Figure 11b: LC³ to Optical Air Eliminator Wiring

LC³

Connect the wires to terminal block J11 on the Lec-

troCount CPU board. Refer to Figure 11b for additional

clarification.

LCR-II

Connect the wires to terminal block J15 on the Lectro-

Count CPU board. Refer to Figure 11a for additional

clarification.

Step 4 - Connect to LectroCount Electronic Register

Route the cables from the optical sensor and solenoid valve

to the back of the LectroCount register. Connect these to two

open ports on the back of the register using the appropriate

connectors.

LCR-II

Connections

Optical Sensor Connection

Wire Color

J15 Pin Connection

Red

56

White

55

Black

54

S3 Solenoid Connection

Terminal

J15 Pin Connection

1 (Red)

52

2 (Black)

53