Installation

Wiring

The optical air eliminator requires a LectroCount LCR/

LCR-II Electronic Register with CPU board part number

81920 (LC³ with 81924). If the LectroCount does not

contain an 81920 CPU board (LC³ with 81924), this board

must be ordered as a replacement to the existing CPU

board.

The 81920 CPU board has an additional connector, con-

nector J15, not present on other board models. On the

LC³ 81924 CPU board it is connector J11.

To make the connection to a LectroCount Register, the

optical sensor comes supplied with a 24” cable. The cable

is potted in the optical sensor assembly at one end. A

threaded cord grip is included to fasten the other end of

the cable into the back of the LectroCount Register. The

solenoid requires a 12 AWG, two-wire, braided cable,

approximately 24 to 36” in length.

!

WARNING

For North American Installations, the installation must be fully in accordance with the National Elec-

trical Code (US) or the Canadian Electrical Code respectively to maintain the hazardous location

ratings on the product. This may involve using rigid conduit for all connections.

!

Caution

Incorrect wiring can damage the optical sensor.

Step 1 - Remove Cable Plug

Loosen and remove the screw from the cover of the S3

solenoid valve cable plug. Remove the cable plug from the

solenoid valve coil. Remove the cover from the cable plug

housing and then remove the terminal block. Be sure to note

its orientation in the housing. Leave the flat gasket in place

on the coil.

Step 2 - Connect Cable to Cable Plug

Route one end of the cable through the conduit fitting and

into the cable plug housing. Connect the cable wires to the

terminal block. Connect the BLACK wire to Terminal 2 and

the RED wire to Terminal 1. These indicators are marked on

the terminal block.