Introduction, How the optical air eliminator works – Liquid Controls Optical Air Eliminator US Patent 7000628 Refined Fuels Applications A8981 & A8981A User Manual

Page 4

Advertising
background image

4

Introduction

How the Optical Air Eliminator Works

A solenoid valve, located at the top of the air eliminator,

is either open or closed. When the liquid level is below

the optical sensor (Figure 1), and a delivery is initiated,

the solenoid valve opens and vents air and vapor to

atmospheric pressure. At the same time, a solenoid-actu-

ated control valve (A2982-11 or A2848-11) closes at the

meter outlet.

When liquid rises to the optical sensor level as the air is

exhausted (Figure 2), the optical air eliminator solenoid

valve closes and prevents continued venting to atmo-

spheric pressure. At the same instant, the control valve

at the meter outlet opens so that a delivery may begin or

continue. This functionality ensures that only liquid passes

through the meter for measurement.

As long as a delivery is active and the liquid level remains

at or above the optical sensor, the optical air eliminator

solenoid valve remains closed and the control valve re-

mains open. If the liquid level should drop below the optical

sensor, the optical air eliminator solenoid valve opens and

the control valve closes. When the delivery is complete,

the control valve closes and the printer prints a delivery

ticket. The optical air eliminator solenoid valve is not ac-

tive between deliveries and remains OFF or closed.

Figure 2: Liquid Level at or above Optical Sensor

Solenoid Valve - OPEN

Vent

Optical Sensor

Control Valve - OPEN

Liquid Level

Figure 1: Liquid Level below Optical Sensor

Solenoid Valve - OPEN

Vent

Optical Sensor

Control Valve - CLOSED

Liquid Level

Advertising