Discontinued – Max Machinery 164 SERIES SIGNAL CONDITIONER_CONVERTER User Manual

Page 4

Advertising
background image

Page 4

164-110-350 Max Machinery, Inc.

1. Connect the flow transmitter with an appropriate Max cable or some other 6 conductor

shielded cable. The shield portion of the cable should be connected at the Model164 only.
The -15V connection should be made for Max 272 Transmitters only.

2. Connect the output(s) to external equipment as desired.

3. Check the board supply jumpers for proper orientation and connect the AC power.

4. If the Model164 was purchased as part of a flow system and calibrated at the factory, the

only control which generally requires attention is the Damping. During operation, set this
adjustment for acceptable display stability at the lowest operational flow rate.

5. Be sure to read the flow meter and transmitter manuals prior to starting up the system.

6. Units which have not been factory calibrated will require further setup. For frequency

input transmitters, the frequency to DC converter will have to be adjusted. For all units,
the range, span and zero controls for the selected output(s) will require calibration.

(For Calibration Instructions, see page 9).

SETUP PROCEDURE

Discontinued