Discontinued – Max Machinery 164 SERIES SIGNAL CONDITIONER_CONVERTER User Manual

Page 6

Advertising
background image

Page 6

164-110-350 Max Machinery, Inc.

Waveform Select (S10): This DIP switch is set to match the transmitter output waveform.

Frequency Range (S9): Set to greater than the maximum expected frequency input from the
transmitter. If S10-5 is set to X2 position, the frequency is multiplied by 2, cutting the
frequency range switch by 1/2.

If S10-5 is on (Xl):

Frequency (Hz) = Maximum flow rate (units/min) x K-factor (pulses/unit)

60

If S10-5 is off (X2):

Frequency (Hz) = Maximum Flow Rate (units/min) x K-factor (pulses/unit)

30

The K-factor can be found on the Flow Meter K-factor Table or calibration sheet.

The voltage out of the frequency to voltage converter is determined by:

Volts = Frequency x 10

S9 Frequency Range

This calculation will be necessary for setting up the output range and span controls.

FREQUENCY TO DC CONVERTER CALIBRATION