Meriam M2110F SMART FLOW GAUGE User Manual

Page 22

Advertising
background image

22

9.8 P8 – DEADBAND

This register is found on the SetPoint model only. The deadband can be set to 0 (disabled), 0.1, 0.2, 0.5, 1, 2, 5 and
10% of full scale flow. The relay will energize at the value in its corresponding P6 and P7 programmable registers
for increasing flow values. The relay will de-energize at a value equal to the corresponding P6 and P7 register,
minus the deadband value for decreasing flow values. With a 0% deadband setting, the relays will energize and
reset precisely at the values in the corresponding P6 and P7 programmable registers. The programming choices
found in the register menu correspond to the actual deadband values in percent full scale.


P#

Name

Description

Value Range

Notes

P8

Deadband

Sets the amount of deadband in
percent of full scale for relays.

0 (disabled), 0.1, 0.2,
0.5, 1, 2, 5, 10%

SetPoint model only.


GAUGE IN MEASURE MODE
1. Press PRGM/ENTER to access P0 prompt
2. If lockout is in-active prompt will be P0

• Increment P# using UP ARROW until P8 is displayed

• Press PRGM/ENTER to access P8 value

• Press the UP or DOWN ARROWS to change the selection

• Press PRGM/ENTER to enter the deadband setting selection

• Press the BACKSPACE to return to MEASURE MODE

3. If lockout is active prompt will be L 00

• Enter Lockout Code then continue as in 2) above

SetPoint Models Only