MOD 30ML Functions

BUILT-IN ANALOG INPUT BLOCK


06

Unacked I/O communications error

(COMMERRU) .................................................... – WR

If the I/O communications error diagnostic is enabled, the unacknowledged diagnostic status
indicates if the diagnostic is or is not acknowledged. The status can be acknowledged or
read as follows.

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

07

Active I/O communications error

(COMMERRA)........................................................... – – R

If the I/O communications error diagnostic is enabled, the active status indicates if the error is
active even after acknowledgement. The status can be read as follows.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.

08

Input Error

(INERRS) ........................................................................................................ CWR

The analog input error diagnostic is a status indication for the built-in circuit. The diagnostic
can be suppressed or enabled as follows.

SUPPRESS

1

Diagnostic error is suppressed. Acknowledgement status remains
clear.

ENABLE

0

Diagnostic error is not suppressed and errors are reported to the
System Event block.

09

Unacknowledged Input error

(INERRU) ......................................................................... – WR

If the analog input error diagnostic is enabled, this unacknowledged status indicates if the
diagnostic is or is not acknowledged. The status can be acknowledged or read as follows.

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

10

Active Input error

(INERRA) ............................................................................................ – – R

If the input error diagnostic is enabled, the active status indicates if the error is active even
after acknowledgement. The status can be read as follows.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.

11

Input Number

(INNUM) .....................................................................................................C – R

The analog input number.

1

The analog input is connected to Input 1 of the built-in circuit.

2

The analog input is connected to Input 2 of the built-in circuit.

12

Error

(ERROR) .................................................................................................................. – WR

Error code indicating the reason for the last input error detected.

0

No

Error

1

Needs Calibration. Analog input requires recalibration.

2

Underrange.

3

Overrange.

4

Error

Unknown.

2-68