Application Builder

CONFIGURATION

AIN

Built-in Analog Input (MOD 30ML). Reference IB-1800R-APP. One of
two available, this block connects its field data using MODOUT to
MODIN of any analog input function block.

AOUT Built-in Analog Output (MOD 30ML). Reference IB-1800R-APP. One of

two available, this block connects an analog outout of some other block
to the field.

5.4.4 Remote Input/Output Module Block Selection

From the Library Display, select Remote Input/Output to make the Remote I/O
modules available as resources. The different types and their associated
hardware modules are:

RIO

Remote I/O Communication Module. Reference IB-23G600 Section
6.2. This module plugs into the instrument and serves as the interface
between it and a CS31 bus. The database must have one RIO block
for each RIO module on the instrument. The RIO module uses CS31
bus address 0.

A connection is required from MODOUT of this block to MODIN of
each remote I/O block in the database that uses this block as the
interface to a CS31 bus. For each of the following, indicate that a
particular channel is used by marking the check box to the left of the
channel number. Enter the bus address of the remote CS31 module
providing the inputs or outputs.

RDIM

Remote Digital Input Module. Reference IB-23G600 Section 6.3. This
block represents one or more digital input channels at an address (1-
31) on a CS31 remote I/O bus. Connect MODOUT of the RIO block to
MODIN of this block. Modules with remote digital inputs are:

ICSI 08 D1 (8 non-isolated 24Vdc input channels)
ICSI 08 E1 (8 isolated 24Vdc input channels)
ICSI 08 E3 (8 isolated 120Vac input channels)
ICSI 16 D1 (16 non-isolated 24Vdc input channels)
ICSI 16 E1 (16 isolated 24Vdc input channels)
ICSK 20 F1 (12 non-isolated 24VDC input channels)
ICSC 08 L1 (8 channels for 24VDC input))

5-9