GENERAL INFORMATION CONTINUED

5

SIGNAL LIGHTS AND ALARM SEQUENCE OF OPERATION

A. "NORMAL" operating mode - truck ICC bar engaged.

1.

The POWERHOLD restraint is in the fully lowered (stored) position. Limit

switch "LS3" is closed.

Outside light = Green

Inside light = Red

Alarm = Off

2.

The POWERHOLD restraint is activated.

a.

The unit leaves the fully lowered (stored) position. Limit switch
"LS3" is open.

Outside light = Red

Inside light = Amber

Alarm = Off

b.

The unit reaches the fully raised ICC bar engaged position, Proxim

ity switches "LS1" and "LS2" are closed.

Outside light = Red

Inside light = Green

Alarm = Off

B. "NORMAL" operating mode - truck ICC bar not engaged.

1.

The POWERHOLD restraint is in the fully lowered (stored) position, Limit

switch "LS3" is closed.

Outside light = Green

Inside light = Red

Alarm = Off

2.

The POWERHOLD restraint is activated.

a.

The unit leaves the fully lowered (stored) position. Limit switch
"LS3" is open.

Outside light = Red

Inside light = Amber

Alarm = Off

b.

The unit reaches the fully raised no ICC bar engaged position.
Proximity switch "LS1" is closed.

Outside light = Red

Inside light = Amber

Alarm = On

(Note: The alarm stays on until the unit reached the lowered position).