6.1.14 Smoke alarms should be interconnected only within the confines of a single

family living unit. If smoke alarms are interconnected between different
units, there may be excessive nuisance alarms. Residents may not be aware
that smoke alarms are being tested or that it is a nuisance alarm caused by
cooking, etc.

6.1.15 Terminals at back of mounting base are marked and coloured as follows:

MARKINGS

(Yellow) 9V 9Vdc POSITIVE POWER SOURCE

(Red) A ACTIVE

(White) SW SWITCH WIRE (FOR INTERCONNECTION ONLY)
(Blue) N NEUTRAL
(Orange) LOOP DEAD TERMINAL

WARNING: Connecting the Switch wire terminal to any other supply conduc-
tor may result in damage to the alarm, failure to operate or shock hazard and
void the warranty of the alarm.

EXAMPLE OF MULTIPLE ALARM WIRING / ISOLATION UNIT WIRING

6. INSTALLATION

LOOP

1

N

9V

SW

A

LOOP

2

SW

9V

A

N

BLUE

ORANGE

ORANGE

YELLOW

WHITE

RED

YELLOW

BLUE

WHITE

RED

24

9V

A SW N

LOOP

MAXIMUM OF 24 SMOKE ALMARMS

CONNECTION TO A

SW

N

FUSE ON
CIRCUIT
BREAKER

SEE INSTALLATION INSTRUCTIONS
FOR LIFSAVER RK10A/9 RELAY MODULE

TO ALARM PANEL

OR

AUXILIARY DEVICES

1398-7208-03:_ 2012.6.13 4:24 PM Page 7