Appendix a - dip switch settings – E-Mon EIDR-16J*RJ User Manual

Page 30

Advertising
background image

INTERVAL DATA RECORDER (IDR)

62-0394-03

30

Appendix A - DIP Switch Settings

The 10-position DIP Switch is used to configure:

• RS-485 Communication protocol (pos 1)

• Ethernet Communication protocol (pos 2)

• RS-485 Baud rate (pos 3 & 4)

• Single channel input mode for RJ45 style connector and ST (screw terminal); dual-

channel only available on RJ45. (pos 5)

• Spare Pos 7 & 8

• RS-485 Bias (pos 9 & 10); only one device on the network needs to have biasing.

The communication baud rate is selected by means of a DIP Switch on the circuit

board. There are four (4) selections: 9600 (factory default), 19.2k, 38.4k, and 76.8k

bps; higher baud rate would reduce cabling length. When connecting the device to an

RS-485 network needing the use of biasing the RS-485 line, turn on DIP Switch pos 9

and pos 10. After changing the DIP switch selections (1.8), restart the device for the

new settings to take effect (9&10 for BIAS doesn’t require CPU restart).

Fig. 8. DIP Switch Baud Rates.

M33277A

3

4

BAUD RATE

ON

ON

9600

OFF ON

19200

ON OFF

38400

OFF OFF

76800

Advertising
This manual is related to the following products: