INTERVAL DATA RECORDER (IDR)

62-0394-03

34

Appendix E - System Wiring Guides

NOTE: METERS 1-8 MUST BE INSTALLED WITHIN 500 FEET OF IDR.

(UP TO 8

METERS)

(UP TO 8

METERS)

~~

4-CONDUCTOR

FLAT MODULAR CABLE

UP TO 4000 FEET TOTAL

DAISY-CHAIN

UP TO 52 IDRS

3 FT USB A TO USB B CABLE

CONNECTS VIA

USB PORT ON PC

PC

RJ-11

6-COND.

RJ-45

RJ-11

6-COND.

RJ-45

6-COND.

RJ-45

IDR A

IDR Z

CONNECTION

CABLE TYPE CONNECTOR

IDR TO E-MON D-MON METERS 1-8 6-COND. 22-26 AWG

RJ-45

(PINS 1 & 8 NOT USED)

IDR TO IDR

4-COND. 26 AWG

RJ-11

IDR TO USB KEY

4-COND. 26 AWG

RJ-11

USB KEY TO COMPUTER**

3 FT USB A to USB B Cable

RJ-45/DTE

IDR TO PULSE METER

2-COND. 14-22 AWG

** SUPPLIED BY E-MON

NOTE: INTERIOR INTERCONNECTING COMMUNICATIONS ARE SUPPLIED WITH THE

PRE-WIRED MMU-TYPE METERING CABINETS.

NOTE: WHEN CONSTRUCTING FIELD-INSTALLED CABLES, MODULAR CABLES MUST BE

MADE SO THAT THE INDIVIDUAL WIRES GO THROUGH ON THE SAME PIN NUMBER.

* CONTACT E-MON FOR USB-ONLY CONNECTION.

AC ADAPTER

AC ADAPTER

USB

KEY*