INTERVAL DATA RECORDER (IDR)

62-0394-03

8

3.0 CONNECTING METERS TO THE IDR

E-Mon D-Mon Meter Connections

a. Each E-Mon D-Mon meter has two modular jacks located at the top of the

main circuit board. The jack on the left (RJ-45, 8-pin) is used to connect the

meter to the IDR.**

NEVER USE 6-PIN JACKS LABELED “PORT 0” OR “PORT 2” TO CON-

NECT A METER TO THE IDR.

b. * All E-Mon D-Mon meters must be connected to meter jacks #1-8 using 6-

conductor flat modular cable.**

c. *IDR-16 - If the IDR is an IDR-16, connect the additional meters to Jacks #9-

16 on the circuit board using 6-conductor flat modular cable.**

d. IDR-8s supplied with plug-in screw type connectors can be up to 500 feet

from all meters, and utilize a pair of wires for connecting to the meter pulse

output.**

* See Appendix D for item B&C above.**

** For more information on cable assembly, see Appendix B.**

Pulse Output Meters (IDR-ST Models Only):

a. Each meter is interfaced with the IDR through the plug-in screw type connec-

tors. Any of the connectors may be used with #22-14 AWG conductors.

b. When used with solid-state switches, correct polarity must be observed in

order for that contact to be recognized. The left terminal of the screw-termi-

nal on the IDR must be connected to the plus (+) side of the switch.

Fig. 4. Meter Connections.

c. The meter can be up to 500 feet away from the IDR.

+

COM SIG

M33472A

IDR TERMINAL

SOLID

STATE

SWITCH