enFORCE

Operation Manual


4.7.4 Synchronized Press Operation

SYNC: Synchronized Press Signal

For using multiple numbers of press units, connect parallel with SYNC common.





























Multiple Press Synchronized Sequence
At the start of the cycle until reaching the synchronization point (1

ST

Load), the SYNC signal is

ON (LOW condition) to stop other Units from continuing to the second step.
When the 1

st

load is reached, the signal works as an input signal (Wired OR). If it reads LOW -

meaning that the other units have not reached 1

ST

Load yet - the unit stays in the standby state

waiting for all connected presses to reach 1

ST

Load. When the SYNC signal is HIGH (all units

have completed the first step), all units simultaneously start the second step.

If a unit is in bypass mode, its SYNC signal stays off (High Condition) to prevent the other units
from being in a waiting condition.

The SYNC signal stays ON (LOW) in the following conditions:

Powering on
After Reset
Emergency Stop
Right after Start

SAN Unit1

6,7 SYNC COM


8,12 SYNC

SAN Unit2

6,7 SYNC COM


8,12 SYNC

SAN Unit3

6,7 SYNC COM


8,12 SYNC

SAN Unit n

6,7 SYNC COM


8,12 SYNC

Chapter 4: System Setup and Wiring