NetworkAIR Rack Air Removal Unit Installation

15

Alarm Settings

The Rack Air Removal Unit has three LEDs on the front of the door that indicate whether the system
is in an alarm state.

LED legend

LED

System

Status

Fan

Status

Thermal Control

Status

Description

Indicates the status of the
controller boards

Indicates status of the three
fans

Indicates the status of the
temperature in the
enclosure

Green

System OK

Fans OK

Temperature within range

Green

Flashing

N/A

N/A

Exhaust temperature has
exceeded the temperature
override setpoint
(kW mode only)

Red

Control failure, the fans
will default to high speed
when there is a board
failure to keep air moving
through the enclosure

Fan failure,
remaining fans operate at
full speed

High temperature, the unit
has lost thermal control

Red/Green

Flashing

N/A

Smoke Alarm (optional)

Smoke Alarm (optional)